10. Please provide further information on temperature setpoints, schedules, minimum flow rates, and ventilation supply flow in Table 1.4, and verify that these are modeled in accordance with Appendix G requirements in the Baseline Case. Please also verify that any Baseline Case system having ventilation rates in excess of 70% and design supply flow in excess of 5,000 cfm has exhaust heat recovery modeled per Section G3.1.2.10, or report the applicable exception that applies to that system.