Dear Nam san, Andy san
CC) Siriruk san
Regarding the trip of TG3, and
your sent data from data logger,
we would like to inform our opinion
after analyzing the data as below,
(Refer to the attached data & graph)
1. The estimated phenomenon of trip
[Analyze of Data]
-1) Data No. 839 14:56:54 Governor Valve Actuator
was stopped.
The possibility for this stopping are
(1) Stop button on TCP push
(2) Electric Supply Source (UPS)
loss or power down
We guessed that the UPS had a problem.
UPS could not supply enough output power to
not only governor actuator motor but also for
instrument such as PLC power.
(Furthermore, regarding the logging system
of TG2, it also on-off repeated by fractured of
the electric source of UPS. so that
UPS for TG2 also to be checked .)
-2) Data No. 840
Gov. Valve Closed, because there is no power of the
governor control after stopping the actuator.
-3) Data No. 841
Speed was reduced and "Low Frequency Alarm"
was occurred.
-4) Data No. 842 (14:57:02)
Turbine Master Trip was occurred by Generator Trip
signal which might be by "AVR Abnormal"
-5) Data No. 848 (14:57:02)
Oil Vapor Extraction Fan was stopped.
It means AC380V was lost.
This is big problem!!
When the TG 3 was tripped, generating power
also stopped and AV380V also lost.
We guess that AC380V is supplied from TG3
by itself, so that TG3 was tripped, AV380V was also
lost.
Please check the line of AC380V source and
to be changed.
-6) Data No. 853 (14:59:06)
Low L.O. Press. Alarm was occurred, but AOP
motor was not started.
(AC380V was lost so that it could not be
started automatically.)
This is also big problem!!
-7) Data No. 854 (14:59:45)
Emergency Oil Pump was run.
(the start pressure of 0.38 kg/cm2g was
found by other data, and this set pressure
of pressure switch to be re-adjusted to
0.4-0.5 kg/cm2g.)
-8) Data No. 857 / 858 / 859 (15:01:18)
Governor valve actuator Run / Stop / Run
It means the electric source of UPS was
fluctuated.
USP could not supply the enough electric power
to PLC for recording the data so that data could not be
recorded in PLC.
-9) Data No. 860 (15:05:24)
USP might be recovered and could supply the
electric source to PLC and start of recording.
2. From the graph
-1) After staring the Emergency LO Pump,
EPO was stopped in only 1 minute operation.
Please check the performance of the
Battery in DC panel.
The performance of battery might be deteriorated.
And at that time, the rotor of Turbine, Gear and
generator were still rotating.
The Lube Oil for all bearing were supplied from
inertial rotating of AOP only.
It will be damaged to each bearings.
Please check and improve soonest possible.
2. AVR Abnormal Indication
After discussing the Nishishiba, the AVR abnormal
might be caused by effect of Residual Voltage of Generator
when the generator stop the generation.
In order to avoid such wrong trip,
we would like to modify the sequence for adding
the timer in the generator control panel.
The detail modification drawing will be forwarded
to you soonest possible.
There are many check points and to be
modified and improved soonest possible.
Your kind understanding and prompt action
for the above would be highly appreciated.
Best Regards,
Dear Nam san, Andy sanCC) Siriruk sanRegarding the trip of TG3, andyour sent data from data logger,we would like to inform our opinion after analyzing the data as below,(Refer to the attached data & graph)1. The estimated phenomenon of trip[Analyze of Data]-1) Data No. 839 14:56:54 Governor Valve Actuatorwas stopped.The possibility for this stopping are(1) Stop button on TCP push(2) Electric Supply Source (UPS) loss or power downWe guessed that the UPS had a problem.UPS could not supply enough output power tonot only governor actuator motor but also forinstrument such as PLC power.(Furthermore, regarding the logging systemof TG2, it also on-off repeated by fractured ofthe electric source of UPS. so thatUPS for TG2 also to be checked .)-2) Data No. 840 Gov. Valve Closed, because there is no power of thegovernor control after stopping the actuator.-3) Data No. 841Speed was reduced and "Low Frequency Alarm"was occurred.-4) Data No. 842 (14:57:02)Turbine Master Trip was occurred by Generator Tripsignal which might be by "AVR Abnormal"-5) Data No. 848 (14:57:02)Oil Vapor Extraction Fan was stopped.It means AC380V was lost. This is big problem!! When the TG 3 was tripped, generating poweralso stopped and AV380V also lost.We guess that AC380V is supplied from TG3by itself, so that TG3 was tripped, AV380V was alsolost.Please check the line of AC380V source and to be changed.-6) Data No. 853 (14:59:06)กด L.O. ต่ำ เตือนภัยเกิดขึ้น แต่ AOPไม่มีเริ่มมอเตอร์(AC380V สูญเสียที่ไม่อาจเริ่มโดยอัตโนมัติ)ยังเป็นปัญหาใหญ่!! -7) ข้อมูลหมายเลข 854 (14: 59:45)ปั๊มน้ำมันฉุกเฉินถูกเรียกใช้(ความดันเริ่มต้นของ 0.38 kg/cm2g ถูกพบข้อมูลอื่น ๆ และความดันชุดนี้ของสวิตช์ความดันที่ต้องปรับปรุงอีกครั้งเพื่อ0.4-0.5 kg/cm2g) -8) ข้อมูลหมายเลข 857 / 858 / 859 (15: 01:18)ผู้ว่าราชการวาล์ว actuator รัน/ หยุด / ทำงานหมายความว่า แหล่งไฟฟ้าของ UPS มาfluctuatedUSP สามารถจัดหาพลังงานไฟฟ้าเพียงพอกับ PLC สำหรับการบันทึกข้อมูลเพื่อให้ ข้อมูลที่ไม่สามารถบันทึกใน PLC-9) ข้อมูลหมายเลข 860 (15: 05:24)USP อาจสามารถกู้คืน และสามารถจัดหาแหล่งไฟฟ้าจำกัด(มหาชน)และเริ่มต้นการบันทึก2. จากกราฟ -1) หลังจากจ้องมองปั๊มหล่อฉุกเฉินEPO ถูกหยุดในเวลา 1 นาทีเท่านั้นกรุณาตรวจสอบประสิทธิภาพของการแบตเตอรี่ในแผง DCประสิทธิภาพของแบตเตอรี่ที่อาจเสื่อมสภาพและ ใน ขณะนั้น ใบพัดของกังหัน เกียร์ และยังมีการหมุนเครื่องกำเนิดไฟฟ้าน้ำมันหล่อลื่นสำหรับแบริ่งทั้งหมดได้มาจากinertial หมุนของ AOP เท่านั้นมันจะเสียหายกับปืนแต่ละกรุณาตรวจสอบ และปรับปรุงเร็วสุด 2. รับผิดปกติข้อบ่งชี้หลังจากคุย Nishishiba, AVR ปกติอาจเกิดจากผลของแรงดันไฟฟ้าส่วนที่เหลือของเครื่องกำเนิดเมื่อเครื่องกำเนิดไฟฟ้าจะหยุดการสร้างเพื่อหลีกเลี่ยงการเดินทางดังกล่าวไม่ถูกต้องเราอยากจะปรับเปลี่ยนลำดับในการเพิ่มจับเวลาในแผงควบคุมของเครื่องกำเนิดไฟฟ้าการปรับเปลี่ยนรายละเอียดที่วาดจะถูกส่งต่อ คุณไปได้เร็วมีหลายจุดและแก้ไข และปรับปรุงเร็วสุดคุณเข้าใจดีและดำเนินการให้ สำหรับด้านบนจะได้ชื่นชมด้วยความเคารพ