Set the range switch to earth voltage position to check earth voltage in the condition of 1. If the indicator swings, earth voltage exists. Make sure that the voltage is 10v or less.
When the display reads more than 10v, it may result in excessive errors in earth resistance measurement . To avoid this, make measurement after reducing the voltage by turning off the power supply of the equipment under test etc.
Simplified measurement