แอร์ LGError code = C1 or CH1Flashing Light = 1Fault = Indoor temperat การแปล - แอร์ LGError code = C1 or CH1Flashing Light = 1Fault = Indoor temperat ไทย วิธีการพูด

แอร์ LGError code = C1 or CH1Flashi

แอร์ LG

Error code = C1 or CH1
Flashing Light = 1
Fault = Indoor temperature sensor open or closed circuit.
Display = Indoor.
Indoor Operation = ON

Error code = C2 or CH2
Flashing Light = 2
Fault = Outdoor temperature sensor open or closed circuit.
Display = Indoor Outdoor.
Indoor Operation = ON

Error code = C4 or CH4
Flashing Light = 4
Fault = Heat sink temperature sensor open or closed circuit.
Display = Indoor Outdoor.
Indoor Operation = ON

Error code = C5 or CH5
Flashing Light = 5
Fault = Communication between indoor and outdoor units.
Display = Indoor Outdoor
Indoor Operation = OFF

Error code = C6 or CH6
Flashing Light = 6
Fault = Excessive current at inverter DC power circuit.
Display = Indoor Outdoor
Indoor Operation = SHUTDOWN

Error code = C7 or CH7
Flashing Light = Excessive compressor current
Fault = 7
Display = Indoor Outdoor
Indoor Operation = SHUTDOWN

Error code = C8 or CH8
Flashing Light = 8
Fault = Indoor fan not rotating.
Display = Indoor
Indoor Operation = OFF

Error code = C9 or CH9
Flashing Light = 9
Fault = Outdoor fan not rotating.
Display = Indoor Outdoor
Indoor Operation = OFF

Error code = CA
Flashing Light = 10
Fault = 1. Discharge temp more than130 °C 2. Faulty discharge thermistor
Display = Indoor Outdoor
Indoor Operation = ON

Error code = CC
Flashing Light = 2+1
Fault = EEPROM error
Display = Outdoor
Indoor Operation = ON

Error code = CD
Flashing Light = 3+1
Fault = Inverter module error
Display = Outdoor
Indoor Operation = ON

Error code = Po
Flashing Light =
Fault = System in Power Mode – not a fault
Display = Indoor
Indoor Operation =

Error code = Lo
Flashing Light =
Fault = System in test mode – not a fault
Display = Indoor
Indoor Operation =


LG Air Conditioning Universal & Multi Split Fault Codes Sheet

Error Code = 01
Contents = Air sensor (open/short)
Case Of Error = Open / Short circuit
Indoor Status = Off

Error Code = 02
Contents = Inlet pipe sensor
Case Of Error = Open / Short circuit
Indoor Status = Off

Error Code = 03
Contents = Communication(Indoor Wired R/Control)
Case Of Error = Communication Poorly
Indoor Status = Off

Error Code = 04
Contents = Drain pump / Float switch
Case Of Error = Float switch Open circuit (High level water alarm)
Indoor Status = Off

Error Code = 05
Contents = Communication(Indoor Outdoor)
Case Of Error = Communication Poorly
Indoor Status = Off

Error Code = 06
Contents = Outlet pipe sensor
Case Of Error = Open / Short circuit
Indoor Status = Off

Error Code = 07
Contents = Different operation mode
Case Of Error = Indoor units set in different operation modes
Indoor Status = Off

Error Code = HL
Contents = High Limit (Float Switch)
Case Of Error = Same as code 04, Float switch Open circuit
Indoor Status = Off


Error Code = CL
Contents = Child Lock Function selected
Case Of Error = Not an error, press Timer & Min buttons simultaneously for 3 seconds to toggle On/Off
Indoor Status = On


Error Code = 21
Contents = IPM Fault (Compressor Over current)
LED01G = 2 times
(Red)
LED02G = 1 time
(Green)
Case Of Error = Compressor malfunction, IPM Fault
Outdoor Status = Off

Error Code = 22
Contents = CT 2 (Max. Current)
LED01G = 2 times
(Red)
LED02G = 2 times
(Green)
Case Of Error = Current is 14A
Outdoor Status = Off

Error Code = 23
Contents = DC Link Low Volt.
LED01G = 2 times
(Red)
LED02G = 3 times
(Green)
Case Of Error = DC Link volt. Is 140V
Outdoor Status = Off


Error Code = 24
Contents = Low / High Pressure
LED01G = 2 times
(Red)
LED02G = 4 times
(Green)
Case Of Error = Low / High press switch OPEN
Outdoor Status = Off

Error Code = 25
Contents = AC Low / AC High Volts.
LED01G = 2 times
(Red)
LED02G = 5 times
(Green)
Case Of Error = Abnormal AC volt. Input.
Outdoor Status = Off

Error Code = 26
Contents = DC Compressor Position
LED01G = 2 times
(Red)
LED02G = 6 times
(Green)
Case Of Error =
Outdoor Status = Off

Error Code = 27
Contents = PSC Fault (Reactor)
LED01G = 2 times
(Red)
LED02G = 7 times
(Green)
Case Of Error =
Outdoor Status = Off

Error Code = 28
Contents = DC Link High Volts
LED01G = 2 times
(Red)
LED02G = 8 times
(Green)
Case Of Error = Off
Outdoor Status = Off

Error Code = 32
Contents = Discharge Pipe Temp. High (INV)
LED01G = 3 times
(Red)
LED02G = 2 times
(Green)
Case Of Error = Off
Outdoor Status = Off

Error Code = 33
Contents = Discharge Pipe Temp. High (Cons.)
LED01G = 3 times
(Red)
LED02G = 3 times
(Green)
Case Of Error = Off
Outdoor Status = Off

Error Code = 40
Contents = CT Circuit
LED01G = 4 times
(Red)
LED02G =
(Green)
Case Of Error = CT Circuit malfunction
Outdoor Status = Off

Error Code = 41
Contents = D-Pipe sensor INV. (Open/Short)
LED01G = 4 times
(Red)
LED02G = 1 time
(Green)
Case Of Error = Open / Short circuit.
Outdoor Status = Off

Error Code = 44
Contents = Air sensor (Open/Short)
LED01G = 4 times
(Red)
LED02G = 4 times
(Green)
Case Of Error = Open / Short circuit.
Outdoor Status = Off

Error Code = 45
Contents = Cond. Pipe Sensor (Open/Short)
LED01G = 4 times
(Red)
LED02G = 5 times
(Gr
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
แอร์ LGError code = C1 or CH1Flashing Light = 1Fault = Indoor temperature sensor open or closed circuit.Display = Indoor.Indoor Operation = ONError code = C2 or CH2Flashing Light = 2Fault = Outdoor temperature sensor open or closed circuit.Display = Indoor Outdoor.Indoor Operation = ONError code = C4 or CH4Flashing Light = 4Fault = Heat sink temperature sensor open or closed circuit.Display = Indoor Outdoor.Indoor Operation = ONError code = C5 or CH5Flashing Light = 5Fault = Communication between indoor and outdoor units.Display = Indoor OutdoorIndoor Operation = OFFError code = C6 or CH6Flashing Light = 6Fault = Excessive current at inverter DC power circuit.Display = Indoor OutdoorIndoor Operation = SHUTDOWNError code = C7 or CH7Flashing Light = Excessive compressor currentFault = 7Display = Indoor OutdoorIndoor Operation = SHUTDOWNError code = C8 or CH8Flashing Light = 8Fault = Indoor fan not rotating.Display = IndoorIndoor Operation = OFFError code = C9 or CH9Flashing Light = 9Fault = Outdoor fan not rotating.Display = Indoor OutdoorIndoor Operation = OFFError code = CAFlashing Light = 10Fault = 1. Discharge temp more than130 °C 2. Faulty discharge thermistorDisplay = Indoor OutdoorIndoor Operation = ONError code = CCFlashing Light = 2+1Fault = EEPROM errorDisplay = OutdoorIndoor Operation = ONError code = CDFlashing Light = 3+1Fault = Inverter module errorDisplay = OutdoorIndoor Operation = ONError code = PoFlashing Light =Fault = System in Power Mode – not a faultDisplay = IndoorIndoor Operation =Error code = LoFlashing Light =Fault = System in test mode – not a faultDisplay = IndoorIndoor Operation =LG Air Conditioning Universal & Multi Split Fault Codes SheetError Code = 01Contents = Air sensor (open/short)Case Of Error = Open / Short circuitIndoor Status = OffError Code = 02Contents = Inlet pipe sensorCase Of Error = Open / Short circuitIndoor Status = OffError Code = 03Contents = Communication(Indoor Wired R/Control)Case Of Error = Communication PoorlyIndoor Status = OffError Code = 04Contents = Drain pump / Float switchCase Of Error = Float switch Open circuit (High level water alarm)Indoor Status = OffError Code = 05Contents = Communication(Indoor Outdoor)Case Of Error = Communication PoorlyIndoor Status = OffError Code = 06Contents = Outlet pipe sensorCase Of Error = Open / Short circuitIndoor Status = OffError Code = 07Contents = Different operation modeCase Of Error = Indoor units set in different operation modesIndoor Status = OffError Code = HLContents = High Limit (Float Switch)Case Of Error = Same as code 04, Float switch Open circuitIndoor Status = OffError Code = CLContents = Child Lock Function selectedCase Of Error = Not an error, press Timer & Min buttons simultaneously for 3 seconds to toggle On/OffIndoor Status = OnError Code = 21Contents = IPM Fault (Compressor Over current)LED01G = 2 times(Red)LED02G = 1 time(Green)Case Of Error = Compressor malfunction, IPM FaultOutdoor Status = OffError Code = 22Contents = CT 2 (Max. Current)LED01G = 2 times(Red)LED02G = 2 times(Green)Case Of Error = Current is 14AOutdoor Status = OffError Code = 23Contents = DC Link Low Volt.LED01G = 2 times(Red)LED02G = 3 times(Green)Case Of Error = DC Link volt. Is 140VOutdoor Status = OffError Code = 24Contents = Low / High PressureLED01G = 2 times(Red)LED02G = 4 times(Green)Case Of Error = Low / High press switch OPENOutdoor Status = OffError Code = 25Contents = AC Low / AC High Volts.LED01G = 2 times(Red)LED02G = 5 times(Green)Case Of Error = Abnormal AC volt. Input.Outdoor Status = OffError Code = 26Contents = DC Compressor PositionLED01G = 2 times(Red)LED02G = 6 times(Green)Case Of Error =Outdoor Status = OffError Code = 27Contents = PSC Fault (Reactor)LED01G = 2 times(Red)LED02G = 7 times(Green)Case Of Error =Outdoor Status = OffError Code = 28Contents = DC Link High VoltsLED01G = 2 times(Red)LED02G = 8 times(Green)Case Of Error = OffOutdoor Status = OffError Code = 32Contents = Discharge Pipe Temp. High (INV)LED01G = 3 times(Red)LED02G = 2 times(Green)Case Of Error = OffOutdoor Status = OffError Code = 33Contents = Discharge Pipe Temp. High (Cons.)LED01G = 3 times(Red)LED02G = 3 times(Green)Case Of Error = OffOutdoor Status = OffError Code = 40Contents = CT CircuitLED01G = 4 times(Red)LED02G =(Green)Case Of Error = CT Circuit malfunctionOutdoor Status = OffError Code = 41Contents = D-Pipe sensor INV. (Open/Short)LED01G = 4 times(Red)LED02G = 1 time(Green)Case Of Error = Open / Short circuit.Outdoor Status = OffError Code = 44Contents = Air sensor (Open/Short)LED01G = 4 times(Red)LED02G = 4 times(Green)Case Of Error = Open / Short circuit.Outdoor Status = OffError Code = 45Contents = Cond. Pipe Sensor (Open/Short)LED01G = 4 times(Red)LED02G = 5 times(Gr
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
แอร์แอลจีรหัสข้อผิดพลาด = C1 หรือ ch1ไฟกระพริบ = 1ผิด = เซ็นเซอร์อุณหภูมิในร่มเปิดหรือปิดวงจรแสดงผล = ในร่มอาคารปฏิบัติการ = บนรหัส C2 C = เกิดข้อผิดพลาดหรือไฟกระพริบ = 2ผิด = เซ็นเซอร์อุณหภูมิกลางแจ้งเปิดหรือปิดวงจรแสดงผล = ในร่มกลางแจ้งอาคารปฏิบัติการ = บนรหัสข้อผิดพลาด = C4 หรือร่างไฟกระพริบ = 4ผิด = เซ็นเซอร์อุณหภูมิความร้อนอ่างเปิดหรือปิดวงจรแสดงผล = ในร่มกลางแจ้งอาคารปฏิบัติการ = บนรหัสข้อผิดพลาด = C5 หรือ ch5ไฟกระพริบ = 5ผิด = การสื่อสารระหว่างหน่วยในร่มและกลางแจ้งแสดงผล = ในร่มกลางแจ้งอาคารปฏิบัติการ = ปิดรหัสข้อผิดพลาด = C6 หรือเชื้อแบคทีเรียไฟกระพริบ = 6ผิด = มากเกินไปในปัจจุบันที่วงจรไฟ dc อินเวอร์เตอร์แสดงผล = ในร่มกลางแจ้งการดำเนินงาน = ปิดร่มรหัสข้อผิดพลาด = C7 หรือดินไฟกระพริบ = คอมเพรสเซอร์ปัจจุบันมากเกินไปผิด = 7แสดงผล = ในร่มกลางแจ้งการดำเนินงาน = ปิดร่มรหัสข้อผิดพลาด ch8 = ดอง หรือไฟกระพริบ = 8ผิด = ร่มพัดลมไม่หมุน= แสดงในร่มอาคารปฏิบัติการ = ปิดรหัสข้อผิดพลาด = C9 หรือ ch9ไฟกระพริบ = 9ผิด = กลางแจ้งพัดลมไม่หมุนแสดงผล = ในร่มกลางแจ้งอาคารปฏิบัติการ = ปิดรหัสข้อผิดพลาด = ซีเอไฟกระพริบ = 10ผิด = 1 จำหน่ายชั่วคราวเพิ่มเติม than130 ° C 2 ผิดพลาดปล่อย thermistorแสดงผล = ในร่มกลางแจ้งอาคารปฏิบัติการ = บนซีซี รหัสข้อผิดพลาดไฟกระพริบ = 2 + 1ข้อผิดพลาด EEPROM ผิด =แสดงผล = กลางแจ้งอาคารปฏิบัติการ = บนรหัสข้อผิดพลาด = ซีดีไฟกระพริบ = 3 + 1ผิด = อินเวอร์เตอร์โมดูลข้อผิดพลาดแสดงผล = กลางแจ้งอาคารปฏิบัติการ = บนรหัสข้อผิดพลาด = โพไฟกระพริบ =ระบบข้อผิดพลาดในโหมดพลังงาน - ไม่ใช่ความผิด= แสดงในร่ม= งานในร่มโล รหัสข้อผิดพลาดไฟกระพริบ =ผิด = ระบบในโหมดทดสอบไม่ผิดจำกัด= แสดงในร่ม= งานในร่มเครื่องปรับอากาศสากลและแบบแยกแผ่นผิดรหัสรหัสข้อผิดพลาด = 01เนื้อหา = เซ็นเซอร์อากาศ ( เปิด / สั้น )กรณีของข้อผิดพลาด = เปิด / ลัดวงจรในสถานะ = ปิดรหัสข้อผิดพลาด = 02เนื้อหา = ท่อท่อเซ็นเซอร์กรณีของข้อผิดพลาด = เปิด / ลัดวงจรในสถานะ = ปิดรหัสข้อผิดพลาด = 03การสื่อสารเนื้อหา = ( Indoor สาย R / ควบคุม )กรณีของข้อผิดพลาด = การสื่อสารไม่ดีในสถานะ = ปิดรหัสข้อผิดพลาด = 04เนื้อหา = ท่อระบายน้ำปั๊ม / ลอยสลับกรณีของข้อผิดพลาด = ลอยสลับเปิดวงจร ( ระดับเตือนน้ำสูง )ในสถานะ = ปิดรหัสข้อผิดพลาด = 05การสื่อสารเนื้อหา = ( ในร่มกลางแจ้งกรณีของข้อผิดพลาด = การสื่อสารไม่ดีในสถานะ = ปิดรหัสข้อผิดพลาด = 06เนื้อหา = ร้านท่อเซ็นเซอร์กรณีของข้อผิดพลาด = เปิด / ลัดวงจรในสถานะ = ปิดรหัสข้อผิดพลาด = 07เนื้อหา = โหมดการดำเนินงานต่าง ๆกรณีของข้อผิดพลาด = หน่วยตั้งในโหมดการดำเนินงานต่าง ๆในร่มในสถานะ = ปิดขายรหัสข้อผิดพลาดเนื้อหา = วงเงินสูง ( สวิตช์ลอย )กรณีของข้อผิดพลาด = เดียวกับรหัส 04 , ลอยสลับวงจรเปิดในสถานะ = ปิดรหัสข้อผิดพลาด = ซีแอลเนื้อหาฟังก์ชันล็อคเด็ก = เลือกกรณีของข้อผิดพลาด = ไม่ใช่ข้อผิดพลาดกดปุ่มพร้อมกันเวลาและนาที 3 วินาทีเพื่อเปิด / ปิดสถานะ = ในร่มรหัสข้อผิดพลาด = 21เนื้อหา = IPM ผิด ( คอมเพรสเซอร์มากกว่าปัจจุบัน )led01g = 2 ครั้ง( สีแดง )led02g = 1 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = เสีย คอมเพรสเซอร์ , IPM ผิดแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 22เนื้อหา = CT 2 ( สูงสุดในปัจจุบัน )led01g = 2 ครั้ง( สีแดง )led02g = 2 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = 14A ในปัจจุบันคือแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 23เนื้อหา = มอเตอร์ต่ำโวลต์led01g = 2 ครั้ง( สีแดง )led02g = 3 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = โวลต์เชื่อม DC เป็น 140vแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 24เนื้อหา = ต่ำ / สูง ความดันled01g = 2 ครั้ง( สีแดง )led02g = 4 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = ต่ำ / สูงกดสวิตซ์เปิดแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 25เนื้อหา = AC ต่ำ / AC สูงโวลต์led01g = 2 ครั้ง( สีแดง )led02g = 5 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = โวลต์ AC ที่ผิดปกติ การป้อนข้อมูลแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 26เนื้อหา = ตำแหน่ง DC คอมเพรสเซอร์led01g = 2 ครั้ง( สีแดง )led02g = 6 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด =แจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 27เนื้อหา = แปลผิด ( เครื่องปฏิกรณ์ )led01g = 2 ครั้ง( สีแดง )led02g = 7 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด =แจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 28เนื้อหา = DC ลิงค์โวลต์สูงled01g = 2 ครั้ง( สีแดง )led02g = 8 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = ปิดแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 32เนื้อหา = temp ท่อปล่อย สูง ( INV )led01g = 3 ครั้ง( สีแดง )led02g = 2 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = ปิดแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 33เนื้อหา = temp ท่อปล่อย สูง ( ข้อเสีย )led01g = 3 ครั้ง( สีแดง )led02g = 3 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = ปิดแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 40วงจร CT = เนื้อหาled01g = 4 ครั้ง( สีแดง )led02g =( สีเขียว )กรณีของข้อผิดพลาด = CT ปกติ วงจรแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 41เนื้อหา = d-pipe เซ็นเซอร์ inv. ( เปิด / สั้น )led01g = 4 ครั้ง( สีแดง )led02g = 1 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = เปิดวงจรแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 44เนื้อหา = เซ็นเซอร์อากาศ ( เปิด / สั้น )led01g = 4 ครั้ง( สีแดง )led02g = 4 ครั้ง( สีเขียว )กรณีของข้อผิดพลาด = เปิดวงจรแจ้งสถานะ = ปิดรหัสข้อผิดพลาด = 45เนื้อหา = โรค . เซนเซอร์ท่อ ( เปิด / สั้น )led01g = 4 ครั้ง( สีแดง )led02g =
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2025 I Love Translation. All reserved.

E-mail: