The fans in the baseline case appear to have a far greater peak design flow than would be expected for a project of this type and size. Please verify that the fan design supply flow was calculated based on a 20 degree supply-air to room-air temperature differential, and that the peak design loads were input correctly into the baseline case energy run. Please also provide a short narrative indicating the factors in the baseline building design that lead to the high fan design flow.