If further sets of temporary overvoltage values and the time of their occurrences are
available as a result of knowing the systems conditions, then for each one the corresponding
rated voltages must be determined separately. If no information is available at
all, then in the case of a solidly earthed neutral, an earth-fault factor of 1.4, and a time
period of ten seconds should be assumed for the occurrence of temporary overvoltages.