- Three-impulse withstand test in which one disruptive discharge on th การแปล - - Three-impulse withstand test in which one disruptive discharge on th ไทย วิธีการพูด

- Three-impulse withstand test in w

- Three-impulse withstand test in which one disruptive discharge on the self-restoring
insulation is tolerated. If this occurs, nine additional impulses are applied during which
no disruptive discharge is tolerated.

- The up-and-down withstand test with seven impulses per level in which disruptive
discharges on self-restoring insulation are tolerated.

- The up-and-down test with one impulse per level, which is recommended only if the
conventional deviation, z, defined in IEC 60-1 is known. The values suggested there,
z = 6 Yo for switching and z = 3 Oh for lightning impulses, shall be used if, and only if, it
is known that ZI 6 % and z 5 3 OX, respectively. Otherwise other methods shall be used.

In all the test procedures described above no disruptive discharge is tolerated on the
non-self-restoring insulation.

No statistical meaning can be given to the three-impulse withstand test in which no
disruptive discharge is tolerated (P, is assumed to be 100 O/.). Its use is limited to cases in
which the non-self-restoring insulation may be damaged by a large number of voltage
applications.

When selecting a test for equipment in which non-self-restoring insulation is in parallel
with self-restoring insulation, serious consideration should be given to the fact that in
some test procedures voltages higher than the rated withstand voltage may be applied and
many disruptive discharges may occur.

5.4 Alternative test situation

When it is too expensive or too difficult or even impossible, to perform the withstand tests
in standard test situations, the apparatus committees, or IEC technical committee 42, shall
specify the best solution to prove the relevant standard withstand voltages. One possibility
is to perform the test in an alternative test situation.

An alternative test situation consists of one or more different test conditions (test
arrangements, values or types of test voltages, etc.). It is necessary, therefore, to
demonstrate that the physical conditions for the disruptive discharge development,
relevant to the standard situation, are not changed.

NOTE - A typical example is the use of a single voltage source for the tests of longitudinal insulation,
while insulating the base, instead of a combined voltage test. In this case, the demonstration mentioned
above concerning the disruptive discharge development is a very stringent condition for the acceptance of
the alternative.

5.5 Phase-to-phase and longitudinal insulation standard withstand voltage tests
for equipment in range I

a) Power-frequency tests

For some equipment with 123 kV 5 U, 2 245 kv, the phase-to-phase (or longitudinal)
insulation may require a power-frequency withstand voltage higher than the phase-toearth
power-frequency withstand voltage as shown in table 2. In such cases the test
shall preferably be performed with two voltage sources. One terminal shall be energized
with the phase-to-earth power-frequency withstand voltage and the other with the
difference between the phase-to-phase (or longitudinal) and the phase-to-earth
power-frequency withstand voltages. The earth terminal shall be earthed.
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
- Three-impulse withstand test in which one disruptive discharge on the self-restoringinsulation is tolerated. If this occurs, nine additional impulses are applied during whichno disruptive discharge is tolerated.- The up-and-down withstand test with seven impulses per level in which disruptivedischarges on self-restoring insulation are tolerated.- The up-and-down test with one impulse per level, which is recommended only if theconventional deviation, z, defined in IEC 60-1 is known. The values suggested there,z = 6 Yo for switching and z = 3 Oh for lightning impulses, shall be used if, and only if, itis known that ZI 6 % and z 5 3 OX, respectively. Otherwise other methods shall be used.In all the test procedures described above no disruptive discharge is tolerated on thenon-self-restoring insulation.No statistical meaning can be given to the three-impulse withstand test in which nodisruptive discharge is tolerated (P, is assumed to be 100 O/.). Its use is limited to cases inwhich the non-self-restoring insulation may be damaged by a large number of voltageapplications.When selecting a test for equipment in which non-self-restoring insulation is in parallelwith self-restoring insulation, serious consideration should be given to the fact that insome test procedures voltages higher than the rated withstand voltage may be applied andmany disruptive discharges may occur.5.4 Alternative test situationWhen it is too expensive or too difficult or even impossible, to perform the withstand testsin standard test situations, the apparatus committees, or IEC technical committee 42, shallspecify the best solution to prove the relevant standard withstand voltages. One possibilityis to perform the test in an alternative test situation.An alternative test situation consists of one or more different test conditions (testarrangements, values or types of test voltages, etc.). It is necessary, therefore, todemonstrate that the physical conditions for the disruptive discharge development,relevant to the standard situation, are not changed.NOTE - A typical example is the use of a single voltage source for the tests of longitudinal insulation,while insulating the base, instead of a combined voltage test. In this case, the demonstration mentionedabove concerning the disruptive discharge development is a very stringent condition for the acceptance ofthe alternative.5.5 Phase-to-phase and longitudinal insulation standard withstand voltage testsfor equipment in range Ia) Power-frequency testsFor some equipment with 123 kV 5 U, 2 245 kv, the phase-to-phase (or longitudinal)insulation may require a power-frequency withstand voltage higher than the phase-toearthpower-frequency withstand voltage as shown in table 2. In such cases the testshall preferably be performed with two voltage sources. One terminal shall be energizedwith the phase-to-earth power-frequency withstand voltage and the other with thedifference between the phase-to-phase (or longitudinal) and the phase-to-earthpower-frequency withstand voltages. The earth terminal shall be earthed.
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
- สามแรงกระตุ้นที่ทนต่อการทดสอบซึ่งเป็นหนึ่งในการปล่อยก่อกวนในตนเองการเรียกคืน
ฉนวนกันความร้อนเป็นที่ยอมรับ ในกรณีนี้เก้าแรงกระตุ้นเพิ่มเติมจะนำไปใช้ในระหว่างที่
ไม่มีการปล่อยก่อกวนเป็นที่ยอมรับ. - ขึ้นและลงทนต่อการทดสอบกับเจ็ดแรงกระตุ้นต่อระดับที่ก่อกวนการปล่อยฉนวนกันความร้อนในการฟื้นฟูตัวเองได้รับการยอมรับ. - ขึ้นและลง การทดสอบกับหนึ่งแรงกระตุ้นต่อระดับซึ่งเป็นที่แนะนำเฉพาะในกรณีที่ส่วนเบี่ยงเบนธรรมดาซีที่กำหนดไว้ในมาตรฐาน IEC 60-1 เป็นที่รู้จักกัน ค่าแนะนำมีซี = 6 โย่สำหรับการเปลี่ยน z และ = 3 โอ้สำหรับแรงกระตุ้นฟ้าผ่าจะนำมาใช้ถ้าหากว่ามันเป็นที่รู้จักกันว่า ZI 6% z และ 5 OX 3 ตามลำดับ มิฉะนั้นวิธีการอื่น ๆ จะถูกนำมาใช้. ในทุกขั้นตอนการทดสอบที่อธิบายข้างต้นไม่มีการปล่อยก่อกวนเป็นที่ยอมรับในฉนวนกันความร้อนที่ไม่ใช่ตนเองการเรียกคืน. ไม่มีความหมายทางสถิติที่จะได้รับการสามแรงกระตุ้นทนต่อการทดสอบที่ไม่มีการปล่อยก่อกวนเป็นที่ยอมรับ (P จะถือว่าเป็น 100 O /.) การใช้งานจะถูก จำกัด ในกรณีที่ฉนวนกันความร้อนที่ไม่ใช่ตนเองการเรียกคืนอาจได้รับความเสียหายเป็นจำนวนมากของแรงดันไฟฟ้าการใช้งาน. เมื่อเลือกสำหรับการทดสอบอุปกรณ์ที่ไม่แสวงหาตนเองการเรียกคืนเป็นฉนวนกันความร้อนในแบบคู่ขนานที่มีฉนวนกันความร้อนในตัวเองการฟื้นฟูอย่างจริงจัง ควรพิจารณาความจริงที่ว่าในขั้นตอนการทดสอบบางส่วนแรงดันไฟฟ้าที่สูงกว่าทนต่อแรงดันจัดอันดับอาจนำมาใช้และการปล่อยก่อกวนหลายคนอาจเกิดขึ้น. 5.4 สถานการณ์การทดสอบทางเลือกเมื่อมันแพงเกินไปหรือยากเกินไปหรือแม้กระทั่งเป็นไปไม่ได้ที่จะดำเนินการทนต่อการทดสอบในสถานการณ์ทดสอบมาตรฐานคณะกรรมการเครื่องมือหรือคณะกรรมการด้านเทคนิค IEC 42 จะระบุทางออกที่ดีที่สุดที่จะพิสูจน์มาตรฐานที่เกี่ยวข้องทนต่อแรงดันไฟฟ้า หนึ่งเป็นไปได้คือการดำเนินการทดสอบในสถานการณ์การทดสอบทางเลือก. สถานการณ์การทดสอบทางเลือกประกอบด้วยหนึ่งหรือมากกว่าเงื่อนไขการทดสอบที่แตกต่างกัน (ทดสอบการเตรียมค่าหรือชนิดของแรงดันทดสอบ ฯลฯ ) มันเป็นสิ่งจำเป็นดังนั้นเพื่อแสดงให้เห็นว่าสภาพทางกายภาพสำหรับการพัฒนาปล่อยก่อกวนที่เกี่ยวข้องกับสถานการณ์มาตรฐานจะไม่เปลี่ยนแปลง. หมายเหตุ - ตัวอย่างทั่วไปคือการใช้แรงดันไฟฟ้าที่แหล่งเดียวสำหรับการทดสอบของฉนวนยาว, ในขณะที่ฉนวน ฐานแทนการทดสอบแรงดันไฟฟ้ารวม ในกรณีนี้การสาธิตดังกล่าวข้างต้นที่เกี่ยวข้องกับการพัฒนาปล่อยก่อกวนเป็นเงื่อนไขที่เข้มงวดมากสำหรับการยอมรับของทางเลือก. 5.5 เฟสต่อเฟสและฉนวนกันความร้อนยาวมาตรฐานการทดสอบการทนต่อแรงดันไฟฟ้าสำหรับงานในช่วงที่ฉัน) การทดสอบพลังงานความถี่สำหรับ อุปกรณ์บางอย่างกับ 123 กิโลโวลต์ 5 U, 245 KV 2 เฟสเฟสไป (หรือยาว) ฉนวนกันความร้อนอาจต้องใช้พลังงานความถี่ทนต่อแรงดันไฟฟ้าที่สูงกว่าเฟส toearth พลังงานความถี่ทนต่อแรงดันไฟฟ้าดังแสดงในตารางที่ 2 ในดังกล่าว กรณีการทดสอบโดยเฉพาะอย่างยิ่งจะต้องดำเนินการกับสองแหล่งที่มาของแรงดันไฟฟ้า ขั้วหนึ่งจะต้องลุ้นกับขั้นตอนเพื่อแผ่นดินพลังงานความถี่ทนต่อแรงดันไฟฟ้าและอื่น ๆ ที่มีความแตกต่างระหว่างขั้นตอนการเฟส (หรือยาว) และเฟสเพื่อแผ่นดินพลังงานความถี่ทนต่อแรงดันไฟฟ้า สถานีแผ่นดินจะต้องต่อสายดิน


















































การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
- สามแรงกระตุ้นทนต่อการทดสอบซึ่งเป็นหนึ่งในองค์กรที่ตนเองปล่อยคืน
ฉนวนจะทนได้ หากปัญหานี้เกิดขึ้น เก้าแรงกระตุ้นเพิ่มเติมจะใช้ในช่วงที่ไม่มีการยอมรับก่อกวน
.

- ขึ้นและลงทนต่อการทดสอบกับเจ็ดแรงกระตุ้นต่อระดับที่ discharges ก่อกวน
ตนเองฟื้นฟูฉนวนจะทน

การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: