Density: The ratio of power supply

Density: The ratio of power supply output power to
the volume of the power supply. Commonly reffered
to as power density.
Derate: See Derating.
Derating: The reduction in output power, voltage
or current required to operate a power supply in an
environment beyond that typically specifi ed. Normally
used to characterize power supply operation
at extended temperatures. See Cooling, Convection
Cooling, Conduction Cooling, Forced Air
Cooling and Free Convection.
Derating Curve: The curve or graph that illustrates
the amount of derating required to operate a power
supply in an abnormal environment.
Dielectric: A material that prevents two points in
an electrical circuit from becoming conductively
connected. At times referred to as a dielectric barrier.
See Conductor.
Dielectric Breakdown: The sudden, destructive,
conduction of current through a dielectric
that occurs when the applied voltage exceeds the
breakdown value. See Dielectric Withstand and
Breakdown Voltage.
Dielectric Strength Test: See High Potential
Test.
Dielectric Withstand Voltage: The maximum voltage
an insulating material can withstand before suffering
punch through or arcing across. See Break
Down Voltage and High Potential Test.
Differential Mode Noise: The noise component
measured between two circuit points with respect to
a common point (minus common mode noise).
Differential Voltage: The difference in voltage
levels measured between two points.
Direct Current: A current that fl ows in one direction.
See Alternating Current.
Discrete Circuit: A circuit or subassembly comprised
of discrete components (resistors, diodes,
FETs, etc.) as opposed to an assembly comprised
of integrated components.
Dissipation: See Internal Power Dissipation.
Distributed Power: A system level architecture,
shown in Figure 10, in which a central supply or
battery system powers an intermediate power bus
(i.e. 24 or 48 VDC). This intermediate bus, routed
throughout the system (normally via a backplane),
provides the input power to a number of DC/DC
converters. These converters in turn provide localized
power (and various voltage levels) to individual
0/5000
จาก: -
เป็น: -
ผลลัพธ์ (ไทย) 1: [สำเนา]
คัดลอก!
Density: The ratio of power supply output power tothe volume of the power supply. Commonly refferedto as power density.Derate: See Derating.Derating: The reduction in output power, voltageor current required to operate a power supply in anenvironment beyond that typically specifi ed. Normallyused to characterize power supply operationat extended temperatures. See Cooling, ConvectionCooling, Conduction Cooling, Forced AirCooling and Free Convection.Derating Curve: The curve or graph that illustratesthe amount of derating required to operate a powersupply in an abnormal environment.Dielectric: A material that prevents two points inan electrical circuit from becoming conductivelyconnected. At times referred to as a dielectric barrier.See Conductor.Dielectric Breakdown: The sudden, destructive,conduction of current through a dielectricthat occurs when the applied voltage exceeds thebreakdown value. See Dielectric Withstand andBreakdown Voltage.Dielectric Strength Test: See High PotentialTest.Dielectric Withstand Voltage: The maximum voltagean insulating material can withstand before sufferingpunch through or arcing across. See BreakDown Voltage and High Potential Test.Differential Mode Noise: The noise componentmeasured between two circuit points with respect toa common point (minus common mode noise).Differential Voltage: The difference in voltagelevels measured between two points.Direct Current: A current that fl ows in one direction.See Alternating Current.Discrete Circuit: A circuit or subassembly comprisedof discrete components (resistors, diodes,FETs, etc.) as opposed to an assembly comprisedof integrated components.Dissipation: See Internal Power Dissipation.Distributed Power: A system level architecture,shown in Figure 10, in which a central supply orbattery system powers an intermediate power bus(i.e. 24 or 48 VDC). This intermediate bus, routedthroughout the system (normally via a backplane),provides the input power to a number of DC/DCconverters. These converters in turn provide localizedpower (and various voltage levels) to individual
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 2:[สำเนา]
คัดลอก!
Density: The ratio of power supply output power to
the volume of the power supply. Commonly reffered
to as power density.
Derate: See Derating.
Derating: The reduction in output power, voltage
or current required to operate a power supply in an
environment beyond that typically specifi ed. Normally
used to characterize power supply operation
at extended temperatures. See Cooling, Convection
Cooling, Conduction Cooling, Forced Air
Cooling and Free Convection.
Derating Curve: The curve or graph that illustrates
the amount of derating required to operate a power
supply in an abnormal environment.
Dielectric: A material that prevents two points in
an electrical circuit from becoming conductively
connected. At times referred to as a dielectric barrier.
See Conductor.
Dielectric Breakdown: The sudden, destructive,
conduction of current through a dielectric
that occurs when the applied voltage exceeds the
breakdown value. See Dielectric Withstand and
Breakdown Voltage.
Dielectric Strength Test: See High Potential
Test.
Dielectric Withstand Voltage: The maximum voltage
an insulating material can withstand before suffering
punch through or arcing across. See Break
Down Voltage and High Potential Test.
Differential Mode Noise: The noise component
measured between two circuit points with respect to
a common point (minus common mode noise).
Differential Voltage: The difference in voltage
levels measured between two points.
Direct Current: A current that fl ows in one direction.
See Alternating Current.
Discrete Circuit: A circuit or subassembly comprised
of discrete components (resistors, diodes,
FETs, etc.) as opposed to an assembly comprised
of integrated components.
Dissipation: See Internal Power Dissipation.
Distributed Power: A system level architecture,
shown in Figure 10, in which a central supply or
battery system powers an intermediate power bus
(i.e. 24 or 48 VDC). This intermediate bus, routed
throughout the system (normally via a backplane),
provides the input power to a number of DC/DC
converters. These converters in turn provide localized
power (and various voltage levels) to individual
การแปล กรุณารอสักครู่..
ผลลัพธ์ (ไทย) 3:[สำเนา]
คัดลอก!
ความหนาแน่น : อัตราส่วนของพลังงานไฟฟ้า

เสียงของแหล่งจ่ายไฟ โดยทั่วไป reffered
เป็นความหนาแน่นพลังงาน derate : ดู derating
.
derating : ลดพลังงาน แรงดันหรือกระแส ต้องใช้

แหล่งจ่ายไฟในสภาพแวดล้อมเกินกว่าที่โดยปกติของเหลวเอ็ด ปกติใช้เพื่อแสดงลักษณะการจัดหาพลังงาน

ที่ขยายอุณหภูมิ ดูความร้อน การพาความร้อน
การระบายความร้อน , เย็น , เย็นและการพาความร้อนแบบบังคับอากาศ

derating ฟรีโค้ง : โค้งหรือกราฟที่แสดงปริมาณของ derating

ต้องใช้พลังงานอุปทานในสภาพแวดล้อมที่ผิดปกติ การใช้วัสดุที่ป้องกัน
:
2 จุด ในวงจรไฟฟ้าเป็น conductively
ที่เชื่อมต่อ บางครั้งเรียกว่าสิ่งกีดขวาง dielectric

ดูคอนดักเตอร์รายละเอียด : อย่างฉับพลัน , การทำลาย , การของกระแสผ่านฉนวน

ซึ่งเกิดขึ้นเมื่อความต่างศักย์เกิน
ค่าแบ่ง เห็นไดอิเล็กทริกและการทนต่อแรงดัน
.
การทดสอบความแข็งแรงของไดอิเล็กทริก : เห็นศักยภาพ
ทดสอบการทนต่อแรงดันสูง

: แรงดันสูงสุดเป็นวัสดุฉนวนสามารถทนก่อนที่ทุกข์
เจาะผ่านหรือ arcing ข้ามเห็นแบ่งแรงดันและศักยภาพสูง
ลงทดสอบ เสียงโหมดเสียงส่วนประกอบ

ค่า : วัดระหว่างสองวงจรจุด ด้วยความเคารพ

จุดทั่วไป ( ลบเสียงโหมดทั่วไป ) .
differential แรงดัน : ความแตกต่างในระดับวัดระหว่างจุดสองจุดที่แรงดัน
.
โดยตรงปัจจุบัน : ปัจจุบันที่ FL ows ในหนึ่ง ทิศทาง

เห็นกระแสสลับ วงจรต่อเนื่อง :วงจรหรือย่อยประกอบด้วย
ส่วนประกอบไม่ต่อเนื่อง ( Resistors , ไดโอด ,
fets ฯลฯ ) ซึ่งตรงข้ามกับการประกอบชิ้นส่วนแบบบูรณาการประกอบด้วย
.
: ดูการกระจายพลังงานภายใน กระจายพลังงาน :

ระดับสถาปัตยกรรมระบบ แสดงในรูปที่ 10 ซึ่งในการจัดหาที่ส่วนกลางหรือ
ระบบแบตเตอรี่พลังเป็น กลางอำนาจรถบัส
( เช่น 24 หรือ 48 VDC ) รถบัสกลางนี้ ถูก
ทั่วระบบ ( ปกติผ่าน Backplane )
ให้สัญญาณไปยังหมายเลขของ DC / DC
ตัวแปลง เหล่านี้ในการเปิดให้บริการแปลง
พลังท้องถิ่น ( และระดับแรงดันต่างๆ ) แต่ละ
การแปล กรุณารอสักครู่..
 
ภาษาอื่น ๆ
การสนับสนุนเครื่องมือแปลภาษา: กรีก, กันนาดา, กาลิเชียน, คลิงออน, คอร์สิกา, คาซัค, คาตาลัน, คินยารวันดา, คีร์กิซ, คุชราต, จอร์เจีย, จีน, จีนดั้งเดิม, ชวา, ชิเชวา, ซามัว, ซีบัวโน, ซุนดา, ซูลู, ญี่ปุ่น, ดัตช์, ตรวจหาภาษา, ตุรกี, ทมิฬ, ทาจิก, ทาทาร์, นอร์เวย์, บอสเนีย, บัลแกเรีย, บาสก์, ปัญจาป, ฝรั่งเศส, พาชตู, ฟริเชียน, ฟินแลนด์, ฟิลิปปินส์, ภาษาอินโดนีเซี, มองโกเลีย, มัลทีส, มาซีโดเนีย, มาราฐี, มาลากาซี, มาลายาลัม, มาเลย์, ม้ง, ยิดดิช, ยูเครน, รัสเซีย, ละติน, ลักเซมเบิร์ก, ลัตเวีย, ลาว, ลิทัวเนีย, สวาฮิลี, สวีเดน, สิงหล, สินธี, สเปน, สโลวัก, สโลวีเนีย, อังกฤษ, อัมฮาริก, อาร์เซอร์ไบจัน, อาร์เมเนีย, อาหรับ, อิกโบ, อิตาลี, อุยกูร์, อุสเบกิสถาน, อูรดู, ฮังการี, ฮัวซา, ฮาวาย, ฮินดี, ฮีบรู, เกลิกสกอต, เกาหลี, เขมร, เคิร์ด, เช็ก, เซอร์เบียน, เซโซโท, เดนมาร์ก, เตลูกู, เติร์กเมน, เนปาล, เบงกอล, เบลารุส, เปอร์เซีย, เมารี, เมียนมา (พม่า), เยอรมัน, เวลส์, เวียดนาม, เอสเปอแรนโต, เอสโทเนีย, เฮติครีโอล, แอฟริกา, แอลเบเนีย, โคซา, โครเอเชีย, โชนา, โซมาลี, โปรตุเกส, โปแลนด์, โยรูบา, โรมาเนีย, โอเดีย (โอริยา), ไทย, ไอซ์แลนด์, ไอร์แลนด์, การแปลภาษา.

Copyright ©2024 I Love Translation. All reserved.

E-mail: