Dielectric breakdown
American Electric Power in Columbus conducted
dielectric breakdown testing on the coils. The coils were
broken down in oil to prevent flashing and arcing.
Requirement was set for the test coils to have breakdown
voltage strength of greater than 70 KV for this 13.8 KV
system.