NOTE: Startability will be improved at temperatures below 0°C(32°F) by the use of a starting aid. A jacket water(coolant heater or other means can be used to heat the engine. NOTICE Do not crank the engine for more than 30 seconds. Allow the starting motor to cool for two minutes before cranking again. The crank cycle time and the total number of crank cycles are programmable. The crank cycle time is the amount of time that the starting motor will be energized and allowed to cool down between cycles. The total number of crank cycles is the number of cycles that are performed. lf the engine does not start within this number of cycles, electrical power to the ECM will be disconnected. This disables the fuel injection system. The OVERCRANK indicator on the instrument panel or on the control panel will illuminate in order to warn of an overcrank. Automatic Starting If the Engine Control Switch(ECS) is in the AUTOMATIC position, the engine will automatically start when a remote start/stop contact is closed. The engine will accelerate to rated speed within a programmed warm-up cycle when the oil pressure sensors indicate there is sufficient oil pressure for rated speed