Another relaying principle uses the differential active power to discriminate between internal faults and other conditions (including magnetizing inrush). Instead of the differential currents, the differential power is computed and monitored [13]. The operating signal is a difference between the instantaneous powers at all the transformer’s terminals.
This approach calls for measuring the voltages at all the terminals, but pays back by avoiding the vector group (angular displacement between the current and voltages at dif