In the fill phase, raw wastewater enters the basin, where it is mixed with settled biomass from the previous cycle. Some aeration may occur during this phase.
Then, in the react phase, the basin is aerated, allowing oxidation and nitrification to occur.
During the settling phase, aeration and mixing are suspended and the solids are allowed to settle.
The treated wastewater is then discharged from the basin in the decant phase. In the final phase, the basin is idle as it waits for the start of the next cycle.
During this time, part of the solids are removed from the basin and disposed of as waste sludge.
Advantages of SBR :
High effluent quality; reduces main pollutants including ammonia by 96%, and reduces phosphates by 88%
SBR operates on a storage and batching system – storing the effluent at peak times in the PST and treating it in small batches throughout the rest of the day – thereby ensuring that each batch receives the full treatment time. Batch system eliminates peak surges
There are no moving parts or electrical components within the tank. All functions within the tank are operated by air power generated by a small compressor/ blower.
Process is simplified. Since all the unit processes are operated in a single tank; final sedimentation tank and return activated sludge pumping are not required,Compact facility; Operation is flexible; nutrient removal can be accomplished by operational changes, Quiescent settling enhances solid separation (low effluent SS), Systems require less space (small foot print) than extended aeration plants-of equal capacity. The system allows for automatic and positive control of mixed liquor suspended solids (MLSS) concentration and solids retention time (SRT) through the use of sludge wasting.
Disadvantages of SBR:
High peal flow can disrupt operation unless accounted for in design,
Batch discharge may require equalization prior to disinfection,
Higher maintenance skills required for instruments, monitoring devices, and automatic valves
It is hard to adjust the cycle times for small communities.
Sludge must be disposed frequently.
Specific energy consumption is high.