LPC-2.A01 module has a lot of settings to customize the application. It's general purpose is to
measure analog values and generate output analog signals.
Module is powered from internal BUS.
Each input or output can be configured as voltage or current type through correspondent jumper.
Inputs have an additional setting for its second terminal voltage. If signal is sourced from outside
active device, then jumper is set to GND. In this case input measures the analog value in reference
to GND. Otherwise, if NTC or other passive sensor is connected to input, jumper should be set to
+10V. If a two wire current device is connected, jumper should be set to +24V (+16V±10%). There are
two jumpers: bottom one is common for first four inputs, top one for last two inputs (refer to Table
2 and Table 3).
The lowest power consumption of LPC-2.A01 module is achieved with ground referenced inputs and
voltage type outputs.
NOTE: For proper system configuration and data allocation please refer to LPC Composer software
help menu.
1