Refer to sheet 5 of drawing 41.8M-BUOY-063-MSB-S-001; M/E Standby LT FW Pump #1(1Q23); we note that the circuit breaker setting of 16AT appears to be insufficient for the service load (40A).
Please be advised that the rating of the disconnecting device is to be coordinated with the
current requirements of the load in accordance to 4-6-4/7.13 of ABS Steel Vessels Rules (Under 90m in Length).