1. Any reasons for you to select multi-cast address: 239.0.38.101 instead of the default 239.0.38.1? It requires the Hotel IT administrator or BAS to provide the networking information.
2. Lutron has so far provided template database of K2A for room 1511. Did you use the same database for all the rooms regardless of room type?
3. The database for K-2A is not yet verified. We require to confirm the database before it can be used for other rooms of the same room type (K-2A).
4. Each Room type will have its temperature database (modification on keypads and zone assignment etc.)
5. It will require to upgrade software and database to include Palladiom Thermostat.
6. Task light and Floor Standing Lamp required to interface with a switch built in the fixture.
7. Lutron require to checkout each type of room to ensure that their database is correct before they are used for other rooms.