Moving the gusset to the bottom flange will require additional kicker supports to prevent
beam rolling and is not preferred.
The loss of weld length in SK-03 due to the beam penetration is acceptable. Per MKA
SSK-02T, a full height stiffener on the opposite side of the brace is also required.
Gussets will need to be removed once platform is no longer in use to accommodate
mechanical duct installation