Figure 7 Device Settings
Within this screen all device settings are accessible. By selecting the appropriate button, the user can:
· Saturation Standard: Select between ANSI 45, ANSI 30, IEC 60044-1, IEC6044-6, or IEC61869
· Color Options: Select the desired colors for Background color, Grid color, Label color,
Knee Marker color, and Saturation traces
· Tolerance Settings: Displays the ratio and phase error limits specified by either ANSI or IEC
· Ratio Error on Primary/Secondary Current: Allows user to select whether the ratio error is
displayed on Primary Current ( 101:5) or
displayed on Secondary Current ( 100:4.99)
· Set Date Time Change the time and date stored in the MRCT
· Show Connection Diagrams: Allows user to turn off the functionality showing connection
Diagrams before each test. This is not recommended because
of safety concerns.
· Knee Prediction Enabled/Disabled: Allows the user to enable and disable the knee point
prediction algorithms. If the user enters the nameplate
information, the MRCT will use this information to
predict the knee point of the CT which can reduce
testing time.
· Demag with AC/DC: Allows user to select the method which the MCRT uses for
demagnetizing a CT. The AC is the default method and is recommended
for most CT’s
· Languages: Select between American English, International English, Spanish,
French, and German, Turkish
· Number Format Select between U.S. and International number formatting
· Default Settings Options: Save changes made to defaults, restore defaults, or
restore factory defaults
· Upgrade Firmware: Upgrade firmware for the MRCT or the STVI
· Display Versions: View all Software and hardware versions of the device.
· Logging: Enable logging, clear all log files, or copy log files to USB
· Adjust Screen Brightness: Change the screen brightness using the manual control knob
· Ethernet: Enable and disable DHCP
· Max Test Voltage: Set the maximum voltage the MRCT will output during a
saturation test
· Saturation Curve Ramp Rate: Allows user to speed up and slow down the rate at which the
voltage is increased during the saturation test. The default is
“1” which sets the speed to normal. By entering a number less
than 1, the ramp rate will be decreased. For example entering
“0.4” will reduce the normal voltage increment by 60%. This
feature can be very useful when a CT saturates very quickly with
minimal voltage increases
v Please note that certain device settings will only be available for manipulation if the user is running the PowerDB application on an STVI ( Smart Touch View Interface ). These settings include: Number Format, Adjust Screen Brightness, Set Date & Time, and Logging. If the application is running on a standard PC or laptop then these settings are adjusted within the PC’s operating system such as Windows.
Figure 7 Device SettingsWithin this screen all device settings are accessible. By selecting the appropriate button, the user can:· Saturation Standard: Select between ANSI 45, ANSI 30, IEC 60044-1, IEC6044-6, or IEC61869· Color Options: Select the desired colors for Background color, Grid color, Label color, Knee Marker color, and Saturation traces· Tolerance Settings: Displays the ratio and phase error limits specified by either ANSI or IEC· Ratio Error on Primary/Secondary Current: Allows user to select whether the ratio error is displayed on Primary Current ( 101:5) or displayed on Secondary Current ( 100:4.99)· Set Date Time Change the time and date stored in the MRCT· Show Connection Diagrams: Allows user to turn off the functionality showing connection Diagrams before each test. This is not recommended because of safety concerns.· Knee Prediction Enabled/Disabled: Allows the user to enable and disable the knee point prediction algorithms. If the user enters the nameplate information, the MRCT will use this information to predict the knee point of the CT which can reduce testing time.· Demag with AC/DC: Allows user to select the method which the MCRT uses for demagnetizing a CT. The AC is the default method and is recommended for most CT’s· Languages: Select between American English, International English, Spanish, French, and German, Turkish· Number Format Select between U.S. and International number formatting· Default Settings Options: Save changes made to defaults, restore defaults, or restore factory defaults· Upgrade Firmware: Upgrade firmware for the MRCT or the STVI· Display Versions: View all Software and hardware versions of the device.· Logging: Enable logging, clear all log files, or copy log files to USB· Adjust Screen Brightness: Change the screen brightness using the manual control knob· Ethernet: Enable and disable DHCP· Max Test Voltage: Set the maximum voltage the MRCT will output during a saturation test · Saturation Curve Ramp Rate: Allows user to speed up and slow down the rate at which the voltage is increased during the saturation test. The default is “1” which sets the speed to normal. By entering a number less than 1, the ramp rate will be decreased. For example entering “0.4” will reduce the normal voltage increment by 60%. This feature can be very useful when a CT saturates very quickly with minimal voltage increases v Please note that certain device settings will only be available for manipulation if the user is running the PowerDB application on an STVI ( Smart Touch View Interface ). These settings include: Number Format, Adjust Screen Brightness, Set Date & Time, and Logging. If the application is running on a standard PC or laptop then these settings are adjusted within the PC’s operating system such as Windows.
การแปล กรุณารอสักครู่..
รูปที่ 7 การตั้งค่าอุปกรณ์ภายในหน้าจอนี้การตั้งค่าอุปกรณ์ทั้งหมดที่สามารถเข้าถึงได้ โดยการเลือกปุ่มที่เหมาะสมผู้ใช้สามารถ: ·มาตรฐานอิ่มตัว: เลือกระหว่าง ANSI 45, ANSI 30, IEC 60044-1, IEC6044-6 หรือ IEC61869 ·ตัวเลือกสีเลือกสีที่ต้องการสำหรับสีพื้นหลังสีตารางสีป้าย , สีเครื่องหมายเข่าและร่องรอยความอิ่มตัว·การตั้งค่าความคลาดเคลื่อนยินยอมแสดงอัตราส่วนและเฟสข้อ จำกัด ข้อผิดพลาดที่ระบุไว้โดยทั้ง ANSI หรือ IEC ·ข้อผิดพลาดอัตราส่วนในระดับประถมศึกษา / มัธยมศึกษาปัจจุบัน: ช่วยให้ผู้ใช้เลือกว่าข้อผิดพลาดอัตราส่วนที่มีการแสดงบนหลักปัจจุบัน(101: 5) หรือแสดงบนรองปัจจุบัน(100: 4.99) ·ตั้งวันที่เวลาเปลี่ยนเวลาและวันที่เก็บไว้ใน MRCT ·แสดงแผนผังการเชื่อมต่อ: ช่วยให้ผู้ใช้ปิดฟังก์ชั่นการแสดงการเชื่อมต่อไดอะแกรมก่อนการทดสอบแต่ละ นี้ไม่แนะนำเพราะ. กังวลด้านความปลอดภัย·ทำนายเข่าที่เปิดใช้งาน/ ปิดการใช้งาน: ช่วยให้ผู้ใช้สามารถเปิดและปิดจุดเข่าขั้นตอนวิธีการทำนาย หากผู้ใช้ป้อนป้ายข้อมูลที่ MRCT จะใช้ข้อมูลนี้เพื่อคาดการณ์จุดที่หัวเข่าของCT ซึ่งสามารถลดการเวลาในการทดสอบ. · Demag กับ AC / DC: ช่วยให้ผู้ใช้สามารถเลือกวิธีการที่ MCRT ใช้สำหรับล้างอำนาจแม่เหล็กทำCT คณะกรรมการตรวจสอบเป็นวิธีการเริ่มต้นและเป็นที่แนะนำให้มากที่สุด CT ของ·ภาษา: เลือกระหว่างอังกฤษอเมริกันอังกฤษ, สเปน, ฝรั่งเศสและเยอรมัน, ตุรกี·รูปแบบจำนวนเลือกระหว่างสหรัฐและจำนวนระหว่างการจัดรูปแบบ·ตั้งค่าเริ่มต้นตัวเลือก: บันทึกการเปลี่ยนแปลงที่เกิดขึ้นกับ เริ่มต้นเรียกคืนค่าเริ่มต้นหรือเรียกคืนเริ่มต้นจากโรงงาน·อัพเกรดเฟิร์มแว: อัพเกรดเฟิร์มแวสำหรับ MRCT หรือ STVI ·แสดงรุ่น:. ดูซอฟแวร์และรุ่นฮาร์ดแวร์ของอุปกรณ์·เข้าสู่ระบบ: เปิดใช้งานเข้าสู่ระบบที่ชัดเจนทั้งหมดล็อกไฟล์หรือคัดลอกไฟล์บันทึก ไปยัง USB ·ปรับความสว่างหน้าจอ: เปลี่ยนความสว่างของหน้าจอโดยใช้ปุ่มควบคุมการใช้·อีเธอร์เน็ต: เปิดใช้งานและปิดการใช้ DHCP ·แม็กซ์ทดสอบแรงดันไฟฟ้า: ตั้งแรงดันไฟฟ้าสูงสุด MRCT จะออกในระหว่างการทดสอบความอิ่มตัว·ความอิ่มตัวCurve อัตราลาด: ช่วยให้ผู้ใช้ความเร็ว และช้าลงอัตราที่ที่แรงดันไฟฟ้าที่จะเพิ่มขึ้นในระหว่างการทดสอบความอิ่มตัวของสี เริ่มต้นคือ"1" ซึ่งกำหนดความเร็วในการเข้าสู่ภาวะปกติ โดยการป้อนหมายเลขน้อยกว่า 1, อัตราลาดจะลดลง ยกตัวอย่างเช่นการป้อน"0.4" จะช่วยลดแรงดันไฟฟ้าปกติเพิ่มขึ้น 60% นี้คุณลักษณะที่จะมีประโยชน์มากเมื่อ CT อิ่มตัวมากได้อย่างรวดเร็วด้วยแรงดันเพิ่มขึ้นน้อยที่สุดโวโปรดทราบว่าการตั้งค่าอุปกรณ์บางอย่างเท่านั้นที่จะสามารถใช้ได้สำหรับการจัดการหากผู้ใช้กำลังใช้งานแอพลิเคชันบนPowerDB STVI (สมาร์ททัชดู Interface) การตั้งค่าเหล่านี้รวมถึงรูปแบบตัวเลข, ปรับความสว่างหน้าจอ, ตั้งวันที่และเวลาและการเข้าสู่ระบบ ถ้าโปรแกรมประยุกต์ที่ทำงานบนเครื่องคอมพิวเตอร์แล็ปท็อปหรือมาตรฐานแล้วการตั้งค่าเหล่านี้จะถูกปรับในระบบปฏิบัติการของเครื่องคอมพิวเตอร์ของเช่น Windows