2. A selection of representative nominal bores may be tested in order to evaluate
the fire resistance of a series or range of mechanical joints of the same design.
When a mechanical joint of a given nominal bore (Dn) is so tested then other
mechanical joints falling in the range Dn to 2xDn (both inclusive) are considered
accepted.