Set constant voltage charger to maximum setting without
exceeding 2.35 VPC. Example: For a target charge of 2.35
VPC on a 24-cell system, you would set the charger
voltage to 56.4 volts.
Depending on the battery’s state of charge, the charger
may go into current limit at the beginning and decline
slowly once the target charge voltage is reached.
B. Record time and current at regular intervals – every hour
as a minimum.
C. Continue charging the battery until there is no further drop
in charge current over 3 consecutive hours. This could
take days if the battery has been in storage for a long time.