4.4.3.2 Equalize charge
Charge parameter
Charge voltage: 2.35~2.40V/cell(25℃)
The maximum charge current:0.25C10
Total variation range of charge voltage:±0.02V/cell
Condition of dropping out the equalizing charge
Reference data of dropping out of the equalizing charge is usually set as 0.01C10,,
multiplied the group No of the battery when it’s parallel connection.