Titanium plate, sheet, forgings, fittings, pipework and tubing shall be unalloyed Grade 1 or 2 where the maximum operating temperature does not exceed 160°F (70°C) and Grade 12 where the maximum operating temperature is in excess of 160°F (70°C). For heat exchanger tubing, the temperature limits shall be defined as the tube metal temperature at the maximum operating temperature.