Good agreement between simulated results and experimental data is obtained.
Effects of the operating parameters (i.e. the pipe material, air velocity) on the thermal performance of earth–air–pipe heat exchanger systems are studied.
The 23.42 mlong EPAHE system discussed in this paper gives cooling in the range of 8.0–12.7 C for the flowvelocities 2–5 m/s.