Law Requirement
Law Title
Notification of Ministry of Industry Re : Fire prevention and
protection in the factory BE 2552 Section 4
Law Regulation
The factory building shall be provided with detection and
fire alarm system throughout the building as appropriate to
local conditions, especially in areas where there is no
active task performance and installation or use electrical
equipment or storage of flammable or combustible
materials are easy to install detection devices and
automatic alarm.
Findings
Smoke detector is not properly installed throughtout the
facility and/ or not regularly maintained.
There was smoke alarm throughout the building but only
available at sample room on 1st floor only. There were no
smoke detector at finished goods area (beside production
building A) and on the 2nd floor of canteen building where
used as temporarily store as required by law.