Consequently, in order to use the dry-air as electrical
insulation medium, pressurization is inevitable. But it is
possible that the liquefaction of water occurs when highly
pressurized condition with high humidity at low temperature.
Liquefaction is the fatal to the dielectric strength of insulation
gas. From the test results, increasing the humidity up to 1,500
PPM shows not remarkable reinforcement of dielectric strength.