Tension figures quoted are tested independently in accordance with B.S. 5080 PART 1 in
approximately 30N/mm² concrete.
The ultimate pull out strength is varied by:
i) The strength of both the substrate and the bar/stub.
ii) The length of the resin bond to bar.
iii) Hole preparation.
iv) Anchor separation.
Safety factors should be considered depending on the strength of hollow blocks and bricks,
tension figures may vary. Site tests should be carried out where necessary to establish particular
suitability. In order to achieve maximum performance, the distance between the centres of the
anchors should be a minimum 2 times the embedment depth and 1.25 times the embedment
depth for the minimum distance from edges.
MIXING RATIO. - 10 : 1 by volume as supplie shelf life of the product.