In addition to the slow increase of the dust concentration a second test is reasonable. The result of the specified measuring campaign was a much faster increase of the dust density compared with the EN54 values, see Fig. 10. A possible second slew rate is proposed to be 0.5 dB/m min. The increase of the dust concentration for the simulation of a fast increasing dust concentration is reasonable within the following limits