Benefits of the WC control system
Due to the implementation of the WC control system,
the average plant production increased 30% with respect
to manual control case, as can be seen in Fig. 14. The
average moisture content of the solid product at the first
dryer outlet decreased from 30% to 23%, as Fig. 15
shows, and the energetic efficiency grown from 70% to
82%, mainly due to the increase in the average inlet temperature
when automatic control. Greater loads of the