Since we don’t have indication of the machine cRABS specifications, we are taking the following
assumptions, which have to be validated by the filling machine manufacturer:
1. The machine manufacturer will supply the RABS with the connections for installing our remote
spray heads according to our installation requirements.
2. The cRABS will be designed to hold VHP processes as far as leak tightness is concerned and will
have connection means to provide aeration through the HVAC system to the outside of the
building.
3. The two chambers will be able to be isolated (a door in the mouse-hole will be provided) in order
to carry out VHP process at different moments.
4. The cRABS shall be designed to withstand positive pressure in order to support the fumigation
process (i.e. values circa 200 Pa).