Smoke detectors/smoke alarms shall
be tested in place to ensure smoke
entry into the sensing chamber and an
alarm response. Testing shall be with
smoke or a listed and labeled product,
acceptable to the manufacturer or in
accordance with their published
instructions. Other methods listed in
the manufacturer’s published
instructions that ensure smoke entry
from the protected area, through the
vents, into the sensing chamber shall be
permitted