I would like help you but how you were able to accumulate so many errors:
1- You have accepted from your supplier a cable which is not in accordance with your command: 12/20KV instead of 12/20(24)KV;
2- You have accepted from your supplier a “Factory Test Report” where the product name “12/20(24)KV XLPE Insulated Power Cable” is not in accordance with the delivered product in particularly some cables where the voltage is not specified on the cable, that is not acceptable;
3- The Factory Test Report doesn’t give the courant leakage value that to be found in the test No.3 “A.C. voltage test 42KV during 5 minutes”?
4- The marking specified by the supplier’s specification “12/20KV CU/XLPE/CWS/PVC Power Cable Zhengzhou Yifang Cable Co., Ltd.” is not in accordance neither with the Product and neither with the Test Report;
Mr. Chatchaval,
You put the life of people in danger with your errors, that is High Voltage installation. If the cable marking is wrong, it must be changed to clarify the question of the danger for all people and particularly for the EDL staff, because this question of danger will reappear in the future year after year and if some people see this sample of installation, may be they will want to put real 12/20KV cables for other 22KV installations because it is cheaper.
I hope that you will take the good resolution for this problems of High Voltage as quick as possible.
I would like help you but how you were able to accumulate so many errors:1- You have accepted from your supplier a cable which is not in accordance with your command: 12/20KV instead of 12/20(24)KV;2- You have accepted from your supplier a “Factory Test Report” where the product name “12/20(24)KV XLPE Insulated Power Cable” is not in accordance with the delivered product in particularly some cables where the voltage is not specified on the cable, that is not acceptable;3- The Factory Test Report doesn’t give the courant leakage value that to be found in the test No.3 “A.C. voltage test 42KV during 5 minutes”?4- The marking specified by the supplier’s specification “12/20KV CU/XLPE/CWS/PVC Power Cable Zhengzhou Yifang Cable Co., Ltd.” is not in accordance neither with the Product and neither with the Test Report;Mr. Chatchaval,You put the life of people in danger with your errors, that is High Voltage installation. If the cable marking is wrong, it must be changed to clarify the question of the danger for all people and particularly for the EDL staff, because this question of danger will reappear in the future year after year and if some people see this sample of installation, may be they will want to put real 12/20KV cables for other 22KV installations because it is cheaper.I hope that you will take the good resolution for this problems of High Voltage as quick as possible.