The I 20/208-V panel board in the example is rated at
100 A; therefore, it must be protected at not more than
100 A, NEC Section 384-16(a). An overcurrent device
must be provided on the secondary side of the transformer
because the transformer is 3 phase and the feeder
consists of more than two wires, NEC Sections 384-