backwash the filter automatically 12) Take measure against zinc dust explosion. Specify what measures to the time of quotation. kind of take at 13) in order to prevent the secondary damage, provide the explosion port. 14) in order to be able to the dust from dust consider the discharge 15) The vendor shall submit the blower specifications at the time of quotation. 16) The blower is mounted on the dust collector itself 17) The vendor shall submit the filter material and its area at the time of quotation 18) The differential pressure indicator and differential pressure switch shall be included in the quotation 19) The dust collector support frame to be included in the vendor's scope. The maintenance deck is in purchaser's scope. However vendor shall submit reforence drawing for the maintenance deck
20) For Information about site weather conditions, refer to the Meteorological data
(3) Control and Operation panel
1) Power: AC480V, 60Hz, 3φ, 1 feeder.
In addition when control power source is required, provide a step-down
transformer inside the panel.
2) Install control panel in the dust collector machine body and deliver.
All electrical wirings for panel, blower etc., to be completed at vendor’s factory,
If there is some wiring to be disconnected for shipping, re-wiring procedure shall be submitted for site installation.
3) The panel shall have communication interface to line PLC for heavy and light failure (motor trips, etc. which includes the operation of the switch) to Line PLC.