Arcing Horns
Forensic Services Newsletter
Aug 2011
Arcing horns on rural HT distribution networks are considered to be a good first line of defense against lightning strikes for both the lines and associated equipment and the downstream transformers to consumers’ premises. Their widespread use in the general overhead distribution networks is justified by both their low cost and their low maintenance factor. For a better level of protection at overhead system entry points into switchyards, the more sophisticated MOV arrestor is used because of its superior ability to divert the lightning surge away from the equipment it is protecting. But because they are considerably much more expensive than pairs of arcing horns they tend to be used only where the equipment being protected is much higher in value and more easily damaged by transients.
Arcing horns on each side of a tension-type insulator string. From Wikipedia article on arcing horns.
Although considered to be old technology and widespread throughout first world rural areas for basic, first-line protection for electrical HT distribution networks against damage from lightning strikes, the omission of the installation of arcing horns, leading to loss of HT equipment in a local consumer’s substation, has recently been encountered. Not only did the consumer suffer sizeable damage to his incoming substation installation, but there was also a considerable loss encountered through business interruption. The simple action of placing arcing horns at the nearest ‘upstream’ and ‘downstream’ support structures from the consumer’s point of connection to the HT supply would have considerably reduced the risk of exposure to damage from a lightning strike entering the distribution system anywhere close by.
Arcing horns protecting bushings on a distribution transformer. From Wikipedia article on arcing horns.
The elevated plateau topography of the area where the distribution network to the consumer’s premises was located made it more than reasonable to consider that it would be prone to lightning strike damage. The facility affected was rurally located and remote from any other buildings or structures that could have presented a favourable alternative ‘target’ for a lightning strike. Considering these aspects, it was a profile that placed this installation in a category where there was a high likelihood of lightning strikes to be expected.
Arcing horns are basically a means of providing an air-gap interposed between the live side of the equipment and earth potential. They present an immediate path to earth accessible across an air-gap ‘tuned’ to the voltage of the circuit they are protecting. The air-gap is set so that dielectric strength of the air between the tip of the earthed electrode and the tip of the electrode connected to the live side of the installation being protected is sufficient to withstand breakdown at the ‘line voltage’ of the installation. When a voltage transient enters the HT distribution system such as that generated by HT switching, or more commonly a lightning strike, the voltage difference across the air-gap exceeds the breakdown voltage across the air-gap. At this point a spark forms which ionizes the air between the electrodes and considerable current flows, maintaining the arc until the potential difference on the line side of the installation has been discharged. This protects the ‘downstream’ equipment from the damaging current flows associated with lightning damage.
The walls of the tank were comprised entirely of thin-walled cooling fins and their sides were no longer flat, but had been slightly bulged at their mid–way between their base and their outer-edge by the explosive expansion of the heated oil from the lightning strike (see the arrows).
Extra high tension transmission lines often have their suspension insulator strings protected with arcing horns in order to divert the lightning discharge to the air gap rather than have the discharges finding their way to earth across the creepage paths on the insulator sheds, thus causing them to shatter with the heating effect from the passage of high levels of current.
Rurally located outdoor transformers are generally protected in this way with arcing horns set up across the HT bushings for the transformer so that any lightning strikes on the HT supply line to the transformer are discharged across the air-gap and are thus prevented from entering the transformer.
The solidified resin from tapes holding the HT windings which had been melted
Search Our Site: SearchFire and ExplosionNon-FireMarine Cargo ClaimsVehicles, CranesLiabilityEquipment RestorationQA and QC ServicesLegalNewsletterSitemapLatest Newsletter : Arcing Hornsask a consultant buttoncraneAdjuster's photograph showing fracture of tower crane during raising.erosionFSM engineer's photograph of fractured diagonal lacing, caused by corrosion.print iconArcing HornsForensic Services NewsletterAug 2011Arcing horns on rural HT distribution networks are considered to be a good first line of defense against lightning strikes for both the lines and associated equipment and the downstream transformers to consumers’ premises. Their widespread use in the general overhead distribution networks is justified by both their low cost and their low maintenance factor. For a better level of protection at overhead system entry points into switchyards, the more sophisticated MOV arrestor is used because of its superior ability to divert the lightning surge away from the equipment it is protecting. But because they are considerably much more expensive than pairs of arcing horns they tend to be used only where the equipment being protected is much higher in value and more easily damaged by transients.Arcing horns on each side of a tension-type insulator string. From Wikipedia article on arcing horns.Although considered to be old technology and widespread throughout first world rural areas for basic, first-line protection for electrical HT distribution networks against damage from lightning strikes, the omission of the installation of arcing horns, leading to loss of HT equipment in a local consumer’s substation, has recently been encountered. Not only did the consumer suffer sizeable damage to his incoming substation installation, but there was also a considerable loss encountered through business interruption. The simple action of placing arcing horns at the nearest ‘upstream’ and ‘downstream’ support structures from the consumer’s point of connection to the HT supply would have considerably reduced the risk of exposure to damage from a lightning strike entering the distribution system anywhere close by.Arcing horns protecting bushings on a distribution transformer. From Wikipedia article on arcing horns.The elevated plateau topography of the area where the distribution network to the consumer’s premises was located made it more than reasonable to consider that it would be prone to lightning strike damage. The facility affected was rurally located and remote from any other buildings or structures that could have presented a favourable alternative ‘target’ for a lightning strike. Considering these aspects, it was a profile that placed this installation in a category where there was a high likelihood of lightning strikes to be expected.Arcing horns are basically a means of providing an air-gap interposed between the live side of the equipment and earth potential. They present an immediate path to earth accessible across an air-gap ‘tuned’ to the voltage of the circuit they are protecting. The air-gap is set so that dielectric strength of the air between the tip of the earthed electrode and the tip of the electrode connected to the live side of the installation being protected is sufficient to withstand breakdown at the ‘line voltage’ of the installation. When a voltage transient enters the HT distribution system such as that generated by HT switching, or more commonly a lightning strike, the voltage difference across the air-gap exceeds the breakdown voltage across the air-gap. At this point a spark forms which ionizes the air between the electrodes and considerable current flows, maintaining the arc until the potential difference on the line side of the installation has been discharged. This protects the ‘downstream’ equipment from the damaging current flows associated with lightning damage.The walls of the tank were comprised entirely of thin-walled cooling fins and their sides were no longer flat, but had been slightly bulged at their mid–way between their base and their outer-edge by the explosive expansion of the heated oil from the lightning strike (see the arrows).Extra high tension transmission lines often have their suspension insulator strings protected with arcing horns in order to divert the lightning discharge to the air gap rather than have the discharges finding their way to earth across the creepage paths on the insulator sheds, thus causing them to shatter with the heating effect from the passage of high levels of current.Rurally located outdoor transformers are generally protected in this way with arcing horns set up across the HT bushings for the transformer so that any lightning strikes on the HT supply line to the transformer are discharged across the air-gap and are thus prevented from entering the transformer.The solidified resin from tapes holding the HT windings which had been melted
การแปล กรุณารอสักครู่..
ค้นหาเว็บไซต์ของเรา :ค้นหาไฟไหม้และการระเบิดไม่มีไฟอ้างการขนส่งสินค้าทางทะเลยานพาหนะ , เครนความรับผิดซ่อมแซมอุปกรณ์บริการ QC QA และกฎหมายจดหมายข่าวเว็บไซต์ข่าวสารล่าสุด : arcing แตรขอปรึกษาปุ่มเครนตั้งเป็นภาพแสดงการแตกของทาวเวอร์เครน ระหว่างเพิ่มการกัดกร่อนในรูปของวิศวกรในแนวทแยงปักหักที่เกิดจากการกัดกร่อนไอคอนพิมพ์arcing แตรบริการนิติข่าวสิงหาคม 2011เครือข่ายกระจาย arcing เขา HT ชนบทถือว่าเป็นบรรทัดแรกของการป้องกันฟ้าผ่า ทั้ง สายและอุปกรณ์อื่นๆที่เกี่ยวข้องกับหม้อแปลงต่อเนื่องไปยังสถานที่ของผู้บริโภค การใช้อย่างแพร่หลายของพวกเขาโดยทั่วไปค่าใช้จ่ายในเครือข่ายการกระจายเป็นคนชอบธรรมโดยทั้งสองของพวกเขา ค่าใช้จ่ายต่ำและปัจจัยการบำรุงรักษาต่ำ สำหรับดีกว่าระดับของการป้องกันที่จุดเข้าระบบค่าใช้จ่ายใน switchyards , arrestor MOV ที่ซับซ้อนมากขึ้นใช้เพราะความสามารถที่เหนือกว่าเพื่อเบี่ยงเบนกระแสฟ้าผ่าห่างจากอุปกรณ์ก็จะป้องกัน แต่เนื่องจากพวกเขามีมากราคาแพงกว่าคู่ของพวกเขามีแนวโน้มที่จะใช้แตร arcing เท่านั้นที่อุปกรณ์ถูกป้องกันสูงขึ้นมากในคุณค่าและเสียหายได้ง่ายขึ้นโดยคนจรจัดแตร arcing ในแต่ละด้านของความตึงเครียดประเภทฉนวนสาย จากบทความวิกิพีเดีย arcing เขซึ่งถือว่าเป็นเทคโนโลยีเก่าและแพร่หลายไปทั่วชนบทโลกครั้งแรกสำหรับพื้นฐาน แถวป้องกันเครือข่ายการกระจายไฟฟ้า HT ต่อความเสียหายจากฟ้าผ่า , ละเว้นการ arcing แตรที่นำไปสู่การสูญเสียของอุปกรณ์ HT ในสถานีย่อยท้องถิ่นของผู้บริโภค มีเมื่อเร็ว ๆนี้พบ ไม่เพียง แต่ผู้บริโภคที่ประสบความเสียหายใหญ่ของเขาเข้ามา อุปกรณ์การติดตั้ง แต่ก็ยังมีการสูญเสียที่พบมากทางธุรกิจหยุดชะงัก ที่ง่ายการกระทำของวาง arcing แตรที่ใกล้ที่สุด " ต้นน้ำ " และ " ล่อง " สนับสนุนโครงสร้างจากจุดของผู้บริโภคของการเชื่อมต่อกับทร. จัดหาจะมากลดความเสี่ยงของการเกิดความเสียหายจากฟ้าผ่าเข้าระบบจำหน่ายที่ใดก็ได้อยู่ใกล้เขาปกป้องกันการ arcing ในหม้อแปลง จากบทความวิกิพีเดีย arcing เขผ่านที่ราบสูง ภูมิประเทศของพื้นที่ที่กระจายไปยังสถานที่ของผู้บริโภคอยู่ทำให้มันมากขึ้นกว่าที่เหมาะสมที่จะต้องพิจารณาว่ามันอาจจะเสี่ยงความเสียหายที่โจมตีสายฟ้า สถานที่ที่ได้รับผลกระทบคือไม่ตั้งอยู่ไกลจากอาคารหรือโครงสร้างอื่นใดที่อาจเสนอทางเลือกที่ดีสำหรับ " เป้าหมาย " เป็นสายฟ้าฟาด พิจารณาแง่มุมเหล่านี้ มันเป็นโปรไฟล์ที่วางติดตั้งนี้ในประเภทที่มีความน่าจะเป็นสูงของฟ้าผ่าได้โดยทั่วไปหมายถึงการ arcing เขาให้มีช่องว่างอากาศ interposed ระหว่างอยู่ด้านข้างของอุปกรณ์ และโลกที่อาจเกิดขึ้น พวกเขาเสนอเส้นทางทันทีเพื่อแผ่นดินสามารถข้ามช่องว่างอากาศ " จูน " แรงดันไฟฟ้าวงจรของพวกเขาจะปกป้อง ช่องว่างอากาศมีการตั้งค่าเพื่อให้ฉนวนความแข็งแรงของอากาศระหว่างปลายของขั้วไฟฟ้า และ earthed ปลายของขั้วไฟฟ้าที่เชื่อมต่อกับอยู่ด้านข้างของการติดตั้งถูกป้องกันเพียงพอที่จะทนต่อการแบ่งสายแรงดันที่ " " ของการติดตั้ง เมื่อแรงดันไฟฟ้าชั่วคราวเข้าสู่ HT ระบบเช่นที่สร้างขึ้นโดย HT สวิตช์หรือมากกว่าปกติ , ฟ้าผ่า , แรงดันไฟฟ้าที่แตกต่างผ่านช่องว่างอากาศเกินแรงดันเบรคดาวน์ในช่องว่างอากาศ . ณจุดนี้จุดประกายรูปแบบซึ่ง ionizes อากาศระหว่างขั้วไฟฟ้าและกระแสไหลมาก , การรักษาอาร์คจนกว่าความต่างศักย์บนเส้นด้านข้างของการติดตั้งได้ถูกปลด นี้จะช่วยปกป้อง " ล่อง " อุปกรณ์เกิดความเสียหายจากกระแสฟ้าผ่าไหลที่เกี่ยวข้องกับความเสียหายผนังของถังประกอบไปด้วยผนังบางเย็นครีบและด้านข้างของพวกเขาไม่แบน แต่ได้รับเพียงเล็กน้อยที่กลาง–ฉุทางระหว่างฐานและขอบนอกของตนเอง โดยระเบิดการขยายตัวของน้ำมันอุ่นจากสายฟ้าฟาด ( ดูลูกศร )เพิ่มสายส่งความตึงเครียดสูงมักจะมีลูกถ้วยสายป้องกันด้วยการ arcing เขาเพื่อเบี่ยงเบนการเกิดฟ้าผ่าในช่องว่างอากาศ แทนที่จะมีการจำหน่ายการหาทางของพวกเขาไปยังโลกข้าม creepage เส้นทางบนฉนวนกันความร้อนหาย จึงก่อให้เกิดการแตกกับความร้อนที่เกิดจากทางเดินของระดับปัจจุบันไม่ตั้งอยู่กลางแจ้งหม้อแปลงโดยทั่วไปจะได้รับการคุ้มครองในลักษณะนี้กับเขาตั้งข้าม arcing ht bushings สำหรับหม้อแปลงไฟฟ้าเพื่อที่สายฟ้าฟาดในทร. จัดหาสายหม้อแปลง ถูกข้ามช่องว่างอากาศ และจึงป้องกันไม่ให้เข้าไปในหม้อแปลงอัตราส่วนผสมเรซินจากเทปถือ HT ขดลวดซึ่งมีละลาย